4-26 Chapter 4: OE2CIH and HART
User’s Manual Pub. 0300272-01 Rev. A.0
Reply Data
HART Ladder Passthrough Query - Reply packet structure
Reply Size = 6 to 260 bytes
Offset
Field
Value
Definition
0
Status
00 = Success
34 = DR_RUNNING
35 = DR_DEAD
Query Status
1
HART Command
0 to 255 (1 byte)
Echo of HART command
2
HART CommStatus
(1 byte)
HART Reply Status Byte #1
3
HART
FieldDeviceStatus
OR
Reason Code if
status = 35
(1 byte)
HART Reply Status Byte #2
Reason Code is a diagnostic value
returned when message fails (Status
= 35)
4
Data Size
0 to 255 (1 byte)
Number of Data bytes in reply for
HART command
5 to
257
HART Reply
Data …
Data bytes returned in data field of
HART reply to requested command
Table 4-18 Flush Ladder Queue (Service Code = 0×50)
Unconnected Message
Field
Value
Definition
Message Type
CIP Generic
Service Code
50
Flush Queues
Class Name
035D
HART Object
Instance
0 = All Channels
1 to n = Single Channel(n-1)
All channels at once
or a single channel
Object Attribute
None, leave this field blank
Request Size
0
No Request Data
Reply Size
0
Number of Data
bytes returned
Request Data
HART Flush Ladder Queue - Request packet structure
Request Size = 0
Offset
Field
Value
Definition
No Request Data
Reply Data
Set Flush Ladder Queue - Reply packet structure
Reply Size = 0 bytes
Offset
Field
Value
Definition
Przeglądanie stron 61