Chapter 4: OE2CIH and HART 4-19
User’s Manual Pub. 0300272-01 Rev. A.0
Request Succeeded Reply
HART Read Dynamic Variables - Reply packet structure
Reply Size = 36 bytes
Command status, 00 = SUCCESS
HART Device reply Status Byte # 1
HART Device reply Status Byte # 2
Status Byte returned from Cmd 9 or
0 for HART rev 5 devices
Primary variable unit code
Secondary variable unit code
Fourth variable unit code
Primary variable assignment code
Secondary variable assignment
code
Third variable assignment code
Fourth variable assignment code
1 byte status from Cmd 9 (Rev 6 or
later)
OR
if Rev 5.x device:
0×C0 = Connected
0×00 = Not Connected
1 byte status from Cmd 9
OR if Rev 5 device:
0×C0 = Connected and Device
provides this value in CMD 3 (that
is, does not truncate)
0×00 = Not Connected
1 byte status from Cmd 9
OR if Rev 5 device:
0×C0 = Connected and Device
provides this value in CMD 3 (that
is, does not truncate)
0×00 = Not Connected