4-14 Chapter 4: OE2CIH and HART
User’s Manual Pub. 0300272-01 Rev. A.0
HART STATUS BITS:
INIT = HART device detected
FAIL = No device found or communication failed
MAFLT = HART does not match analog loop current
MSGRDY = Ladder pass-through message available
DDLDR = Device Data update Ladder
DDLGX = Device Data update Logix
SUA = Status Update Available, Cmd 48 data changed
FAULT= HART device reports a fault
HART STATUS BYTE 1: Communication Status / Response Code
This if the first status byte returned in a Slave-to-Master frame. It is used for both
Communication Status and Response Code. If the Most Significant Bit is set a
communication error has been reported by the device. Otherwise the remaining 7 bits
contain the response code.
Bits 6..0 = Enum 0 to 127, command-
dependent
Longitudinal Parity Error
HART STATUS BYTE 2: Field Device Status
This is the second status byte returned in a Slave-to-Master frame:
Non-Primary Variable Out of Limits
Primary Variable Out of Limits