Spectrum-controls 1769sc-IF8u Instrukcja Użytkownika Strona 20

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 126
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 19
10 Compact IO
Universal Input module
3. Wiring the module
4. Configuring the module
5. Going through the startup procedure
6. Monitoring module operation
Step 1: Ensure that your 1769 system
power supply(1) has sufficient current
output to support your system configuration. Reference
Chapter 3
(Installation and Wiring)
The modules maximum current draw is shown below
5V dc 24V dc
150 mA 45 mA
NOTE The module cannot be located more than 8 modules away from
the system power supply.
(1) The system power supply could be a 1769-PA2, -PB2, -PA4, -PB4, or the internal
supply of the MicroLogix 1500 packaged controller.
Step 2: Attach and lock the module. Reference
Chapter 3
(Installation and Wiring)
NOTE The module can be panel or DIN rail mounted. Modules can be
assembled before or after mounting.
Przeglądanie stron 19
1 2 ... 15 16 17 18 19 20 21 22 23 24 25 ... 125 126

Komentarze do niniejszej Instrukcji

Brak uwag