Spectrum-controls 1769sc-IF8u Instrukcja Użytkownika Strona 116

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 126
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 115
106 Compact IO
Universal Input Module
!
When using the read IO configuration feature in RSLogix, you
need to manualy enter 18 into the “extra data length” field.
To configure the module select the Generic Extra Data Configuration
tab. Enter the decimal equivalent of each configuration word. There are
a total of 18 words that need to be configured altogether. The module
default settings are used if all the configuration words are left at zero..
NOTE For a complete description of each of these parameters and the
choices available for each of them, refer to chapter 4.
NOTE: Words 10 through 17 are reserved and must contain zero.
Przeglądanie stron 115
1 2 ... 111 112 113 114 115 116 117 118 119 120 121 ... 125 126

Komentarze do niniejszej Instrukcji

Brak uwag