26 SLC 500
Isolated Analog Output Modules
Table 11. Channel status word details, Input Words 4 through 7 (I:e.4 through I:e.7)
These bit settings in the status word Indicate this
Bit: 15 14 13 12 11 10 9 8 7654 3210
0 Output channel disabled
1 Output channel enabled
0 0 1 1–5 Vdc output range
0 1 0 0–5 Vdc output range
0 1 1 0–10 Vdc output range
1 0 0 0–20 mA output range
1 0 1 4–20 mA output range
1 1 0 0–21 mA output range
0 0 0 Engineering units
0 0 1 Scaled for PID
0 1 0 Proportional counts
0 1 1 1746-NO4 format
1 1 0 User-defined scale
0 Reset output on fault
1 Hold last value on fault
0 No output data limiting
1 Output data limiting
0 No error
1 Operating temperature error
0 No error
1 Over-limit error
0 No error
1 Under-limit error
0 No error
1 Over-range error
0 No error
1 Under-range error
0 No error
1 Non-fatal channel error
0 No error
1 Fatal channel error