Spectrum-controls 1746sc-INO4vi Instrukcja Użytkownika Strona 34

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
Przeglądanie stron 33
24 SLC 500
Isolated Analog Output Modules
Figure 5. Example relationship between output signal and
channel data
Data Value
9999
100
20.5 mA3.5 mA
Signal
Value
In the preceding example...
S
low
= 3.5 U
low
= 100
S
high
= 20.5 U
high
= 9999
S = 17 U = 9899
Controlling Each Output
Channel’s Signal
Output words 0 through 3 determine the output signal levels for channels
0 through 3, respectively. The output signal level depends on the output
range and data format selected.
Channel 0 Output Data Word
15
0
O:e.0
Address
Channel 1 Output Data WordO:e.1
Channel 2 Output Data WordO:e.2
Channel 3 Output Data WordO:e.3