Przeglądanie stron 25
Micro800™ 4 Ch Universal Thermistor Input Module 26
Publication 0100198-01 Rev. A
Environmental
Tests
Industry Standards
Test Level Limits
EFT/B immunity
(Performance
Criteria B)
IEC 61000-4-4
Signal Ports:
± 3 kV @ 5 kHz for 5
minutes, Criteria B
(Marine?)
± 2 kV @ 5 kHz for 5
minutes, Criteria A
(Marine?)
± 2 kV @ 5 kHz for 5
minutes, Criteria B
(standard)
Power Ports:
± 2 kV @ 5 kHz for 5
minutes, Criteria A
(Marine?)
± 2 kV @ 5 kHz for 5
minutes, Criteria B
(standard)
Surge transient
immunity
(Performance
Criteria B)
IEC 61000-4-5
Signal Ports:
± 2 kV line-earth
{CM}@ 2Ω on
shielded ports
Power Ports
± 2 kV CM @ 12 Ω
± 1 kV DM @ 2 Ω
Conducted RF
immunity
(Performance
Criteria A)
IEC 61000-4-6
10 V rms with 1 kHz
sine wave 80% AM
from 150 kHz…80
MHz on signal and
power ports
Magnetic Field
(Performance
Criteria A)
IEC 61000-4-8
30 A rms/m
AC Mains Voltage
Dips, Interruptions
and Variations
IEC 61000-4-11
Follow the 61000-4-
11.