Spectrum-controls 1762sc-OF8 Instrukcja Użytkownika Strona 36

  • Pobierz
  • Dodaj do moich podręczników
  • Drukuj
  • Strona
    / 42
  • Spis treści
  • BOOKMARKI
  • Oceniono. / 5. Na podstawie oceny klientów
Przeglądanie stron 35
A-2 MicroLogix™ 1200 IO 8 Ch Output Module
User’s Manual Pub. 0300246-01 Rev. B
Specification Value
Product Code 21
Agency
Certification
C-UL listed (under CSA C22.2 No. 142)
UL 508 listed
CE compliant for all applicable directives
Hazardous
Environment
Class
Class I, Division 2, Hazardous Location, Groups A, B,
C, D
(ISA 12.12.01, C-UL under CSA C22.2 No. 213)
Operating Temperature Code T6
Radiated and
Conducted
Emissions
EN55011
Electrical /EMC: The module has passed testing at the following levels:
ESD Immunity
(IEC61000-4-2)
4 kV contact, 8 kV air, 4 kV indirect
Radiated Immunity
(IEC61000-4-3)
10 V/m, 80 to 1000 MHz, 80% amplitude modulation,
+900 MHz keyed
carrier
Fast Transient
Burst
(IEC61000-4-4)
2 kV, 5 kHz
Surge Immunity
(IEC61000-4-5)
1 kV galvanic gun
Conducted
Immunity
(IEC61000-4-6)
10V, 0.15 to 80 MHz
8
8
Conducted Immunity frequency range may be 150 kHz to 30 MHz if the Radiated Immunity frequency range is 30 MHz to 2700
MHz.