28 SLC 500
Isolated Analog Input Modules
Configuring Each Input
Channel
After installing your module, you must configure each channel by setting
bit values in each configuration word. Output words 0 through 3 of the
output image file (addresses O:e.0 through O:e.3) configure channels 0
through 3, respectively.
15
Channel 0 Configuration Word
0
O:e.0
Address
Channel 1 Configuration WordO:e.1
Channel 2 Configuration WordO:e.2
Channel 3 Configuration WordO:e.3
Important - After reconfiguring a channel, you must toggle the channel
enable bit (configuration bit 0) in order for your module to use the new
configuration.