Chapter 3: Configuring the 1734sc-IExCH for RSLogix 5000 3-17
User’s Manual Pub. 0300257-01 Rev. A
Table 3-5 (IE4CH Input Assembly)
104
100
101
102
103
Analog + Hart 0,1,2,3
Analog Only
Analog + Hart 0
Analog + Hart 0,1
Analog + Hart 0,1,2
112 Bytes RSL5K (DNet 108 bytes)
16 Bytes RSL5K (Dnet 12 bytes)
40 Bytes RSL5K (Dnet 36 bytes)
64 Bytes RSL5K (DNet 60 bytes)
88 Bytes RSL5K (DNet 84 bytes)
( instance 104 is the default, instances 100-103 are subsets available to conserve bandwidth )
Analog data
12 bytes
0x00-0x0B
Channel 0 Data - INT
Channel 1 Data - INT
Channel 2 Data - INT
Channel 3 Data - INT
Status Byte for Channel 1 Status Byte for Channel 0
OR
UR
HHA
LLA
HA
LA
CM
CF
OR
UR
HHA
LLA
HA
LA
CM
CF
Status Byte for Channel 3 Status Byte for Channel 2
OR
UR
HHA
LLA
HA
LA
CM
CF
OR
UR
HHA
LLA
HA
LA
CM
CF
Ch. 0 Hart Data
24 bytes
0x0C-0x23
Input Ch 0 Hart Device Status Byte 1
Input Ch 0 Hart Device Status Byte 0
Response Code
1
FAULT
SUA
DDLGX
DDLDR
MSGRDY
MAFLT
FAIL
INIT
Input Ch 0 Hart Device Status Byte 3
Extended Device Status Byte
3
Input Ch 0 Hart Device Status Byte 2
Field Device Status Byte
2
Input Channel 0 Hart PV - REAL (float)
Input Channel 0 Hart SV - REAL (float)
Input Channel 0 Hart TV - REAL (float)
Input Channel 0 Hart FV - REAL (float)
Input Channel 0 Hart SV Status Input Channel 0 Hart PV Status
Input Channel 0 Hart FV Status Input Channel 0 Hart TV Status
Ch .1 Hart
0x24-0x3B
(Data structure same as channel 0 above, 24 bytes)
Ch.2 Hart
0x3C-0x53
(Data structure same as channel 0 above, 24 bytes)
Ch.3 Hart
0x54-0x6B
(Data structure same as channel 0 above, 24 bytes)