Chapter 1: Module Overview 1-3
User’s Manual Pub. 0300257-01 Rev. A
1.5.1 LED Indicators
The 1734 analog HART module uses several LEDs to show operational status. The
status LEDs are defined below:
Table 1-1 (LED Status Indicators)
Indicator State Description
Module Status
Off No power applied to device
Green Device operating normally
Flashing Green Device needs commissioning due to configuration
missing, incomplete, or incorrect
Flashing Red Unrecoverable fault may require device replacement.
Red Recoverable fault.
Flashing Red/Green
Device is in self-test mode.
Network status
Off Device is not on-line
- Device has not completed dup_MAC_id test.
- Device not powered - check module status indicator
Flashing Green Device is on-line but has no connections in the
established state.
Green Device on-line and has connections in the established
state.
Flashing Red One or more I/O connections in timed-out state
Red Critical link failure - failed communication device.
Device detected error that prevents it communicating
on the network.
Flashing
Red/Green
Communication faulted device - the device has
detected a network access error and is in
communication faulted state.
Channel status
Off Channel not in use
Solid Green Normal (channel scanning inputs)
Flashing Green Channel receiving HART data
Solid Red No power or major channel fault
Flashing Red Channel at end of range
Flashing Red/Green
Hart device error on HART enabled channel
Section 1.6
System
Overview
The module communicates to the controller via a 1734 Control Net, Device Net or
Ethernet adapter. The module receives 5 and 24V dc power through the bus interface.
Note: No external power supply is required for 2-wire input transmitters.
1.6.1 Module Power-up
At power-up, the module performs a check of its internal circuits, memory, and basic