Installation Instructions
32-Channel Analog Input Module
Quantum Series 140 AxI 05x 00sc
45
STEP 4: Check the module’s communication status.
VERIFY: The module’s green ACTIVE LED is on. This indicates that
the module is communicating properly with the rack.
CORRECTIVE ACTION:
Set the rack into run mode.
Reinstall the module in the rack.
STEP 5: Check the module’s health status.
VERIFY: The module is reported as healthy in the Modsoft I/O map
Screen. Check to make sure that the module description, slot location, and
register assignments are correct. Also, verify that the module is recog-
nized and reported as healthy. If an asterisk is present before the
module’s name, then the module is not recognized by the rack.
CORRECTIVE ACTION:
Reinstall the module in the rack.
Reselect the module in the I/O Map using the <Shift + ?> key. If the
module is not listed, install the Modsoft Runtime files included with
your module.
STEP 6: Check the module’s register operation.
VERIFY: The 4X configuration word and the 3X+8 Status word are
setup properly. As a quick check, disable all ladder programming and set
the 4X register to 0000 Hex and verify that the 3X+8 Status register
cycles through the values 0000, 0001, 0010, and 0011 Hex.
CORRECTIVE ACTION:
Check steps 1 through 6 above and then call Spectrum Controls
Customer Satisfaction at (425) 746-9481.