4-4 Compact™ IO Isolated RTD/Resistance Module
User’s Manual Pub. 0300241-01 Rev. A
4.2.4 Selecting Data Formats (Bits 12 through 14)
This selection configures channels 0 through 5 to present analog data in any of the
following formats:
• Raw/Proportional Data
• Engineering Units x 1
• Engineering Units x 10
• Scaled for PID
• Percent Range
Table 4-3 (Channel Data Word Format)
Input
Type
Data Format
Engineering Units x 10 Engineering Units x 1
Scaled
For
PID
Proportional Counts Percentage
˚ Celsius ˚ Fahrenheit ˚ Celsius ˚ Fahrenheit
Pt 385 -200 to +850 -328 to 1562 -2000 to +8500 -3280 to 15620 0 to 16383 -32767 to 32767 0 to 10000
Pt 3916 -200 to +630 -328 to 1166 -2000 to +6300 -3280 to 11660 0 to 16383 -32767 to 32767 0 to 10000
10 Cu 426 -100 to +260 -148 to 500 -1000 to +2600 -1480 to 5000 0 to 16383 -32767 to 32767 0 to 10000
100 Ni 618 -100 to +260 -148 to 500 -1000 to +2600 -1480 to 5000 0 to 16383 -32767 to 32727 0 to 10000
120 Ni 672 -80 to +260 -112 to 500 -800 to +2600 -1120 to 5000 0 to 16383 -32767 to 32767 0 to 10000
604 NiFe 518 -100 to +200 -148 to 392 -1000 to +2000 -1480 to 3920 0 to 16383 -32767 to 32767 0 to 10000
150 ohm
0 to +1500
5
0 to +15000
5
0 to 16383 -32767 to 32767 0 to 10000
500 ohm
0 to +500
5
0 to +5000
5
0 to 16383 -32767 to 32767 0 to 10000
1000 ohm
0 to +1000
5
0 to +10000
5
0 to 16383 -32767 to 32767 0 to 10000
3000 ohm
0 to +3000
5
0 to +30000
5
0 to 16383 -32767 to 32767 0 to 10000
Note: The engineering units data formats represent real engineering temperature
units provided by the module to the controller. The raw/proportional counts, scaled-
for-PID and percent of full-scale data formats may yield the highest effective
resolutions, but may also require that you convert channel data to real engineering
units in your control program.
Raw/Proportional Data
The value presented to the controller is proportional to the selected input and scaled into
the maximum data range allowed by the bit resolution of the A/D converter and filter
selected. The raw/proportional data format also provides the best resolution of all the
data formats.
If you select the raw/proportional data format for a channel, the data word will be a
number between -32767 and +32767. For example, if a Pt 385 RTD is selected, the
5
When resistances are selected, the temperature setting is ignored and the input data is the same for either °C or
°F selection.